- Feet
- None
- Weight
- 21.000 Kg
- Approvals
- CE
- Port size
- NPT 3/8
- Flow switch
- F (w/Flow Switch)
- Pipe Thread
- N (NPT)
- Power Supply
- W2 (200 to 240 VAC)
- Tank capacity
- 1.3 L
- Control method
- Cooling/Heating automatic shift PID control
- Cooling method
- Water-cooled refrigeration
- Cooling Capacity
- 012 (1.2 kW)
- Cooling capacity
- 1200 W
- Heating capacity
- 2000 W
- Circulating fluid
- Tap water, Ethylene glycol 20%
- Power Consumption
- 1200 W
- High-pressure pump
- P (High-pressure Pump Mounted)
- Current consumption
- 7 A (200V) to 6 A (240V)
- General power supply
- Single-phase 200 to 240 VAC ±10 %, 50/60 Hz
- Set temperature range
- 10 to 60 °C
- Temperature stability
- ± 0.01 to 0.03 °C
- Facility water port size
- NPT 3/8
- Maximum ambient temperature
- 35 °C
- Minimum ambient temperature
- 10 °C
- Facility water pressure range
- Within 1 MPa
- Facility water temperature range
- 10 to 35 °C
- Contact material for facility water
- Stainless steel 304
- Contact material for circulating fluid
- Stainless steel, EPDM, NBR, Ceramics, PPE, PPS, Carbon, PP, PE, Nylon, POM, PVC
- Facility water requiered flow range (50 Hz)
- 10 to 15 l/min